EstimationPro AI EstimationPro AI

Free Voltage Drop Calculator - NEC Wire Run Check (2026)

Free voltage drop calculator for electricians. Enter wire gauge, amps, distance, and voltage to check NEC compliance. Supports copper, aluminum, single-phase, and three-phase circuits.

1,000+ Contractors Reviewed by Pros By EstimationPro Team
Wire Material

Current draw or breaker size

Panel to load, one direction

Phase

NEC recommends 3% for branch circuits, 5% total

6.6%Voltage Drop

Exceeds 3% Limit

7.92V drop over 100 ft (12 AWG copper)

Minimum gauge needed: 500 kcmil

Voltage Drop Results

Voltage Drop7.92 V
Voltage Drop %6.60%
Voltage at Load112.1 V
Wire Resistance1.98 Ω/1,000 ft

Distance & Sizing

Max Distance at 3%45 ft
Current Distance100 ft
Min Gauge for 3%500 kcmil

NEC Voltage Drop Guidelines

2%
Strict
3%
Branch
5%
Total

Based on NEC Chapter 9, Table 8 resistance values. NEC 210.19(A) and 215.2(A) recommend limiting voltage drop. Always verify with your local AHJ.

Last updated: March 31, 2026

12,800+ estimates calculated this month

How to Use This Calculator

Select your wire gauge and material

Choose the AWG wire size you plan to install or are checking (14 AWG through 500 kcmil). Select copper or aluminum conductor. The calculator uses resistance values from NEC Chapter 9, Table 8.

Enter amperage and one-way distance

Type the circuit amperage (match your breaker size for branch circuits) and the one-way distance from the panel to the load in feet. This is the single-direction run, not the total wire length.

Set voltage, phase, and drop limit

Select your system voltage (120V residential, 240V appliances, 208V/480V commercial). Choose single-phase or three-phase. The NEC recommends 3% max for branch circuits and 5% max for the combined feeder and branch circuit.

Review voltage drop and recommendations

The calculator shows your voltage drop in volts and percentage, the voltage delivered at the load, and the maximum distance your wire can run within the limit. If you exceed the limit, it recommends the minimum wire gauge that will pass.

Voltage Drop Formulas

Single-Phase: Vdrop = (2 × L × I × R) ÷ 1,000
Three-Phase: Vdrop = (√3 × L × I × R) ÷ 1,000
Vdrop % = (Vdrop ÷ Source Voltage) × 100

Where:

L
= One-way conductor length in feet (panel to load)
I
= Circuit current in amps
R
= Wire resistance in ohms per 1,000 ft (NEC Chapter 9, Table 8)
Vdrop
= Voltage lost across the conductor run (volts)

Free to Embed on Your Website

Add this calculator to your blog, resource page, or client portal — just copy one line of code. Your visitors get a useful tool, you get more engagement.

100% freeAuto-resizesMobile responsiveNo sign-up required
EstimationPro AI For Contractors, By Contractors

From Calculations to Client-Ready Estimates

You have the technical specs. Now build a professional estimate that wins the job.

Photos & voice to estimate PDF proposals & schedules Regional pricing data
No credit card required Set up in under 2 minutes Trusted by contractors nationwide

Frequently Asked Questions

What is voltage drop and why does it matter?

Voltage drop is the loss of voltage as electrical current flows through a conductor over distance. Every wire has resistance, and that resistance converts some energy to heat instead of delivering it to the load. Excessive voltage drop causes motors to overheat, lights to dim, and equipment to malfunction. The NEC recommends keeping voltage drop within limits to ensure equipment operates safely and efficiently. On long runs to outbuildings, shops, or well pumps, voltage drop is often the factor that determines wire size, not ampacity.

What does the NEC say about voltage drop limits?

NEC 210.19(A) Informational Note No. 4 and 215.2(A) Informational Note No. 2 recommend a maximum of 3% voltage drop for branch circuits and 5% total for the combined feeder and branch circuit. These are recommendations, not hard code requirements. However, most inspectors and engineers treat 3% as the practical limit for branch circuits. Some jurisdictions enforce stricter limits. Always check with your local authority having jurisdiction (AHJ).

How do I calculate voltage drop?

The formula for single-phase voltage drop is: Vdrop = (2 x L x I x R) / 1000, where L is the one-way distance in feet, I is the current in amps, and R is the wire resistance in ohms per 1,000 feet from NEC Table 8. For three-phase circuits, replace the 2 with 1.732 (square root of 3). The "2" in single-phase accounts for the current traveling out on the hot conductor and returning on the neutral. Divide the voltage drop by the source voltage and multiply by 100 to get the percentage.

What is the difference between copper and aluminum wire for voltage drop?

Aluminum wire has roughly 1.6x the resistance of copper wire at the same gauge. That means aluminum produces more voltage drop per foot. To compensate, you typically need to go up two wire sizes when switching from copper to aluminum. For example, if a circuit needs 6 AWG copper, you would use 4 AWG aluminum to achieve similar voltage drop performance. Aluminum is cheaper per foot but requires more material, so the cost difference depends on the run length and current prices.

When does voltage drop matter more than ampacity?

Voltage drop becomes the controlling factor on long wire runs, typically over 100 feet. A 12 AWG copper wire is rated for 20 amps, but at 200 feet on a 120V circuit, the voltage drop hits 6.6%, well over the 3% recommendation. You would need to upsize to 8 AWG or even 6 AWG to keep voltage drop within limits, even though 12 AWG handles the ampacity just fine. This is common with detached garages, outbuildings, well pumps, and landscape lighting circuits.

Does voltage drop apply to DC circuits?

Yes. The single-phase formula (Vdrop = 2 x L x I x R / 1000) works for DC circuits as well, since DC current flows out on one conductor and returns on another. This is especially relevant for solar panel installations, battery systems, and low-voltage landscape lighting where long runs at 12V or 24V can produce significant percentage drops even with relatively low resistance wire.

Related Tools

Why Contractors Choose EstimationPro AI

Estimates in 60 Seconds

AI generates detailed, line-item estimates from basic project details. No more hours on spreadsheets.

Accurate Pricing Data

Built on real contractor pricing and industry cost databases, updated for 2026 market conditions.

Professional Proposals

Send polished PDF estimates with your branding. Clients see a professional contractor they can trust.

Get Paid Faster

Built-in invoicing and Stripe payments. Collect deposits and progress payments directly from estimates.

Related Free Tools

Turn specs into client-ready estimates